Product Description
Output Ratings
|
Voltage, Frequency
|
|
Prime
|
Standby |
230 V, 50 HzKW
|
kVA
|
6.8
|
7.5 |
kW
|
6.8 |
7.5 |
Ratings at 1 power factor.
Please refer to the output ratings technical data section for specific
generator set outputs per voltage.
Dimensions and Weights
|
Length
|
mm
|
1550 (61) |
Width
|
mm |
620 (24.4) |
Height
|
mm |
1020 (40.2) |
Weight (Dry)
|
kg |
233 (514) |
Weight (Wet)
|
kg |
238 (525) |
Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no
limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
Standby Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is
permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
Standard Reference Conditions
Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity.
Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
FG Wilson offer a range of optional features to allow you to tailor our generator sets to meet your power needs.
Options available include:
• Upgrade to CE Certification
• A wide range of Sound Attenuated Enclosures
• A variety of generator set control and synchronising panels
• Additional alarms and shutdowns •
A selection of exhaust silencer noise levels
For further information on all of the standard and optional features accompanying this product please contact your local Dealer or visit:

*: Heat radiated from engine and alternator
Designed to operate in ambient conditions up to 50°C (122°F).
Contact your local FG Wilson Dealer for power ratings at specific site conditions.
Reactances shown are applicable to prime ratings.
*Based on 30% voltage dip at 0.9 power factor.
** With optional independant excitation system (PMG / AUX winding)

Documentation
Operation and maintenance manual including circuit wiring diagrams.
Generator Set Standards
The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22.
Warranty
6.8 - 750 kVA electric power generation products in prime applications the warranty period is 12 months from date of start-up, unlimited hours (8760). For standby
applications the warranty period is 24 months from date of start-up, limited to 500 hours per year.
730 - 2500 kVA electric power generation products in prime applications the warranty period is 12 months from date of start-up, unlimited hours (8760 hours) or 24
months from date of start-up, limited to 6000 hours. For standby applications the warranty period is 36 months from date of start-up, limited to 500 hours per year.
FG Wilson manufactures product in the following locations:
Northern Ireland • Brazil • China • India
With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.
To contact your local Sales Office please visit the FG Wilson website at www.fgwilson.com.
FG Wilson is a trading name of Caterpillar (NI) Limited.
In line with our policy of continuous product development, we reserve the right to change specification without notice.